AS Series Module Manual _3 3-6 CR# Name Description Defaults 4 Channel 4 mode setup 6: 0 mA–20 mA 7: 4 mA–20 mA 5 Channel 1 offset Range: -32768 to +32767 0 6 Channel 2 offset 7 Channel 3 offset 8 Channel 4 offset 9 Channel 1 gain Range: -32768 to +32767 1000 10 Channel 2 gain 11 Channel 3 gain 12 Channel 4 gain 13 Retaining an output sent by channel 1 0: when the PLC stops, the value of the analog output is reset to 0. 1: when the PLC stops, the value of the analog output is retained. 0 14 Retaining an output sent by channel 2 15 Retaining an output sent by channel 3 16 Retaining an output sent by channel 4 17 Refreshing the time for an output sent by channel 1 Range:
10–3200 (100 ms–32000 ms) Unit: 10 ms Any value less than 10 is processed as 0. Any value larger than 3200 is processed as 3200. Set the value to 0 to disable this function. 0 18 Refreshing the time for an output sent by channel 2 19 Refreshing the time for an output sent by channel 3 20 Refreshing the time for an output sent by channel 4 21 The minimum scale range for channel 1 For digital-analog modules, it is much more convenient if the system can convert digital values to floating-point values for earier understanding. Here you can set the minimum and maximum scale ranges of corresponding floating-point values for channels.
For example, if the scale range for a digital to analog output channel is ±10.0 V, it indicates the maximum -10.0 22 23 The minimum scale range for channel 2 -10.0 24 25 The minimum scale range for channel 3 -10.0 26 27 The minimum scale range -10.0