Chapter 3 Analog Output Module AS04DA 3_ 3.2.5 Functions 1. Enable/Disable a Channel An analog signal is converted into a digital signal at a rate of 2 ms per channel. The total conversion time is 2 ms X (the number of channels). If a channel is not used, you can disable it to decrease the total conversion time. 3-7 CR# Name Description Defaults 28 for channel 4 value is +10.0 V and the minimum value is -10.0 V. If the scale range for a digital to analog output channel is 4 mA ~ 20 mA. It indicates the maximum value is 20 mA and the minimum value is 4 mA. When the format is set to integer in HWCONFIG, the scale range is invalid.
You can also use PLC instruction DSCLP (API0217) and set SM685 to ON to use floating-point operations. 29 The maximum scale range for channel 1 10.0 30 31 The maximum scale range for channel 2 10.0 32 33 The maximum scale range for channel 3 10.0 34 35 The maximum scale range for channel 4 10.0 36 37 Channel alarm setup 0: warning 1: alarm bit0: error in the power supply bit1: error in the module hardware bit2: error in calibration 0 Item Function Description 1 Enable/Disable a Channel 1. Enable or disable a channel. 2. If a channel is disabled, the total conversion time decreases. 2 Calibration Calibrate a linear curve.
3 Retain an Output When a module stops running, the system can retain the signal sent by the module. 4 Refresh Time for an Output Refresh the analog output value according to the value of the fixed slope. 5 Scale Range You can set the scale range when the format is floating-point.