AS Series Module Manual 2. Calibration To make a curve meet specific needs, calibrate the curve by changing the offset and the gain. The calibration range depends on the range of inputs that the hardware can receive. The formula is: Example: A channel receives voltage inputs between -10.0 V to +10.0 V. The gain is 1000, and the offset is 0. The _3 corresponding value for the original signal -10.0 V to +10.0 V is -32000 to +32000. If you change the offset to -100, the calibrated value for the original signal -10.0 V to +10.0 V becomes -31900 to +32100. Signals after the calibration -32 000 32100 Voltage (Y) Analog signal 3.
Retain an Output When a module stops running, the system can retain the signal sent by the module. The output is retained: Input signal Output signal Module stops running Time 3-8 10V 0 -31900 Original sign 3200 0 3 Digital val -10V