AS Series Module Manual _5 5-10 CR# Name Description Atr. Defaults 23 Output channel 1 mode setup 0: closed 1: -10 V to +10 V (default) 2: 0–10 V 3: -5 V to +5 V 4: 0–5 V 5: 1–5 V 6: 0–20 mA 7: 4–20 mA R/W 1 24 Output channel 2 mode setup 25 Output channel 1 offset Range: -32768 to +32767 R/W 0 26 Output channel 2 offset 27 Output channel 1 gain Range: -32768 to +32767 R/W 1000 28 Output channel 2 gain 29 Retain the output sent by channel 1 0: When the PLC stops, the value of the analog output is reset to 0. 1: When the PLC stops, the value of the analog output is retained. R/W 0 30 Retain the output sent by channel 2 31 Refresh the time for output sent by channel 1 Range:
10–3200 (100 ms–32000 ms) Unit: 10 ms Any value less than 10 is read as 0. Any value larger than 3200 is read as 3200. Set the value to 0 to disable this function. R/W 0 32 Refreshing the time for an output sent by channel 2 R/W 0 33 The minimum scale range for input channel 1 When the format is set to integer in HWCONFIG, the scale range is invalid. For analog-digital modules, it is much more convenient if the system can convert digital values to floating-point values for earier understanding. Here you can set the minimum and maximum scale ranges of corresponding floating-point values for channels.
For example, if the scale range for an analog to digital input channel is ±10.0 V, it indicates the maximum value is +10.0 V and the minimum value is -10.0 V. R -10.0 34 35 The minimum scale range for input channel 2 -10.0 36 37 The minimum scale range for input channel 3 -10.0 38 39 The minimum scale range for input channel 4 -10.0 40 41 The minimum scale range for output channel 1 -10.0 42 43 The minimum scale range for output channel 2 -10.0 44