Delta Electronics — 5.2.4 Control Registers

Chapter 5 Analog Input/Output Module AS06XA 5_ 5-11 CR# Name Description Atr. Defaults 45 The maximum scale range for input channel 1 If the scale range for an analog to digital input channel is 4 mA ~ 20 mA. It indicates the maximum value is 20 mA and the minimum value is 4 mA. Note: You can use PLC instruction DSCLP (API0217) and set SM685 to ON to use floating-point operations when a conversion range needs to edit.

10.0 46 47 The maximum scale range for input channel 2 10.0 48 49 The maximum scale range for input channel 3 10.0 50 51 The maximum scale range for input channel 4 10.0 52 53 The maximum scale range for output channel 1 10.0 54 55 The maximum scale range for output channel 2 10.0 56 201 Instruction Set Instructions for peak values 16#0101: record the peak value again for channel 1 16#0102: record the peak value again for channel 2 16#0104: record the peak value again for channel 3 16#0108: record the peak value again for channel 4 16#010F: record the peak values again for channels 1–4 16#0201: enable recording for channel 1 16#0202: enable recording for channel 2 16#0204:

enable recording for channel 3 16#0208: enable recording for channel 4 16#020F: enable recording for channels 1–4 16#0211: disable recording for channel 1 16#0212: disable recording for channel 2 16#0214: disable recording for channel 3 16#0218: disable recording for channel 4 16#021F: disable recording for channels 1–4 16#0502: restore default settings W 0