Delta Electronics — 5.2.6 Wiring

AS Series Module Manual 5.2.6 Wiring  Precautions To ensure the analog-to-digital module functions well and reliably, the external wiring must prevent noise. Before you install the cables, follow the precautions below. (1) To prevent a surge and induction, the AC cable and the input signal cables that are connected to the AS06XA-A must be separate cables. (2) Do not install the cable near a main circuit, a high-voltage cable, or a cable connected to a load that is not a PLC. In addition, the cable must not be bound to a main circuit, a high-voltage cable, or a cable connected to a load which is not a PLC. (3) Ground shielded cables and hermetically sealed cables separately.

(4) Terminals with insulation sleeves cannot be arranged as a terminal block, so you should cover the terminals with insulation tubes. (5) Use single-core cables or twin-core cables with a diameter of 24–22 AWG and with pin-type _5 connectors smaller than 1 mm. Only use copper conducting wires which can withstand temperatures of 60° C /75° C or higher. 24-22AWG 8-10mm (6) Note: use cables with the same length (less than 200 m) and use wire resistance of less than 100 ohm. (7) Notes on two-wire, three-wire, and four-wire connections:  Two-wire connection/three-wire connection (passive transducer): connect the transducer and the analog input module to the same power circuit.

 Four-wire connection (active transducer): the transducer uses an independent power supply, so do not connect it to the same power circuit as the analog input module. 5-20