AS Series Module Manual 6.2.4 AS04RTD Control Registers *If you use HWCONFIG to set values in CRs, once the set value is downloaded, the values can be retained in the module; however if you use TO instruction to write data into CRs, the values CANNOT be retained, after power failure or after transition of the CPU from STOP to RUN. Note: The attribute of the CR must be W (write) to use TO instruction. _6 6-6 CR# Name Description Atr. Defaults 0 Format Setup 0: integer format 1: floating point format R 0 1 Channel 1 mode setup 0:
closed 1:0–300 Ω (default) 2:0–3000 Ω 3:Pt100 4:JPt100 5:Pt1000 6:Ni100 7:Ni1000 8:LG-Ni1000 9:Cu50 10:Cu100 R/W 1 2 Channel 2 mode setup 3 Channel 3 mode setup 4 Channel 4 mode setup 5 Channel 1 offset Range: -32768 to +32767 R/W 0 6 Channel 2 offset 7 Channel 3 offset 8 Channel 4 offset 9 Channel 1 gain Range: -32768 to +32767 R/W 1000 10 Channel 2 gain 11 Channel 3 gain 12 Channel 4 gain 13 Channel 1 average times Range: 1–100 R/W 10 14 Channel 2 average times 15 Channel 3 average times 16 Channel 4 average times 17 Channel 1 filter average percentage Range: 0–3 Unit: ±10% R/W 1 18 Channel 2 filter average percentage