Delta Electronics — 6.2.4 AS04RTD Control Registers

Chapter 6 Temperature Measurement Module AS04/06RTD 6_ 6-7 CR# Name Description Atr. Defaults 19 Channel 3 filter average percentage 20 Channel 4 filter average percentage 21 Units of temperature 0: Fahrenheit 1: Celsius R/W 0 22 Channel alarm setup 0: open channel alarm 1: close channel alarm bit0: channel 1 bit1: channel 2 bit2: channel 3 bit3: channel 4 0: warning 1: alarm bit8: error in the power supply bit9: error in the module hardware bit10: error in calibration R/W 0 201 Instruction set 16#0101: record the peak value again for channel 1 16#0102: record the peak value again for channel 2 16#0104: record the peak value again for channel 3 16#0108:

record the peak value again for channel 4 16#010F: record the peak values again for channels 1–4 16#0201: enable recording for channel 1 16#0202: enable recording for channel 2 16#0204: enable recording for channel 3 16#0208: enable recording for W 0