Delta Electronics — 6.2.6 Functions

Chapter 6 Temperature Measurement Module AS04/06RTD 6.2.6 Functions Use the HWCONFIG utility software built into ISPSoft to set modes of operation and parameters.  Analog input 6_ 1. Enable/Disable a Channel An analog signal is converted into a digital signal at a rate of 200 ms per channel. If a channel is not used, you can disable it to decrease the total conversion time. 2. Unit of Measurement Select the unit of measurement, Fahrenheit or Celsius, according to your needs. 3. Calibration  To make a curve meet specific needs, calibrate the curve by changing the offset and the gain. The calibration range depends on the range of inputs that the hardware can receive. The formula is:

𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂= (𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼Ч 𝐺𝐺𝐺𝐺𝐺𝐺𝐺𝐺) 1000 + 𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂𝑂 6-15 Item Function Description 1 Enable/Disable a Channel 1. Enable or disable a channel. 2. If a channel is disabled, the total conversion time decreases. 2 Unit of Measurement Select the unit of measurement: Fahrenheit or Celsius. 3 Calibration Calibrate a linear curve. 4 Average Conversion values are averaged and filtered. 5 Disconnection Detection If the channel is open, the module can detect when it is disconnected. If the input is open-circuited, the module produces an alarm or a warning.

6 Channel Detection and Alarm If an input signal exceeds the range of inputs that the hardware can receive, the module produces an alarm or a warning. You can disable this function. 7 Limit Detections for Channels Save the maximum/minimum values for channels. 8 Records for Channels Save the analog curves for channels. 9 PID Algorithm PID control modes