Chapter 6 Temperature Measurement Module AS04/06RTD *1. Use shielded twisted pair cables for temperature sensors, and keep them away from power cables and other cables that generate noise. *2. If using two-wire temperature sensors, L n - and I n - must be short-circuited (where n is between 1–4). *3. There are two different internal excitation currents. If you are using a Ni100 temperature sensor, a Pt100 sensor, a JPt100, a Cu50/Cu100, or a 0~300 Ω resistance sensor, the internal excitation current is 1.5 mA. If you are using a Ni1000 temperature sensor, a Pt1000 temperature sensor, a LG- Ni1000 sensor, or a 0~3000 Ω resistance sensor, the internal excitation current is 0.2 mA. Note:
When using a three-wire temperature sensor, the cables should be the same length (less than 200 meter) and with a resistor less than 20 ohm. (2) AS06RTD-A 6_ *1. Use shielded twisted pair cables for temperature sensors and keep them away from power cables and other cables that generate noise. *2. Terminal “I12-“ indicates “ I1- & I2-“, terminal “I34-“ indicates “ I3- & I4-“, and terminal “I56-“ indicates “ I5- & I6-“. If you use two-wire temperature sensors, Ln- and In- must be short-circuited (where n is between 1–6). *3. There are two different internal excitation currents.
If you are using a Ni100 temperature sensor, a Pt100 sensor, a JPt100, a Cu50/Cu100, or a 0~300 Ω resistance sensor, the internal excitation Ni1000 sensor, or a 0~3000 Ω resistance sensor, the internal excitation current is 0.2 mA. current is 1.0 mA. If you are using a Ni1000 temperature sensor, a Pt1000 temperature sensor, a LG- Note: When using a three-wire temperature sensor, the cables should be the same length (less than 200 meter) and with a resistor less than 20 ohm.
6-19 0~300Ω , 0~3000Ω Ni100/Ni1000/Pt100/Pt1000 Cu50/Cu100/JPt100/LG-Ni1000 CH1 L L S 2-Wire Shielded cable *1 CH2 L L I1 3-Wire Shielded cable *1 Ni100Pt100,J P,t100, Cu50, C u100/ Ni1000, P t1000, LG-Ni1000 *3 1+ ADC 1- LD INA 2+ 2- 2- *2 A G L 1- S LD L L 2+ 2- I1 2-