Delta Electronics — 6.2.8 Wiring

AS Series Module Manual 6.2.7 Control Mode 1. Refer to section 7.2.7 for more details on how to use DMPID instruction. 2. When using PID parameters to set up control registers: PID control registers of AS04RTD-A are retainable; however PID control registers of AS06RTD-A are not retainable. 6.2.8 Wiring  Precautions To ensure the analog-to-digital module functions well and reliably, the external wiring must prevent noise. Before you install the cables, follow the precautions below. (1) To prevent a surge and induction, the AC cable and the input signal cables that are connected to the ASRTD Series must be separate cables.

(2) Do not install the cable near a main circuit, a high-voltage cable, or a cable connected to a load which is not a PLC. In addition, the cable must not be bound to a main circuit, a high-voltage cable, or a cable connected to a load which is not a PLC. (3) Ground shielded cables and hermetically sealed cables separately. (4) Terminals with insulation sleeves cannot be arranged as a terminal block, so you should cover the terminals with insulation tubes. (5) Note: use cables with the same length (less than 200 m) and use wire resistance of less than 20 _6 ohm.

 External wiring (1) AS04RTD-A 6-18 0~300Ω , 0~3000Ω Ni100/Ni1000/Pt100/Pt1000 Cu50/Cu100/JPt100/LG-Ni1000 CH1 L L I Shielded cable *1 SL 2-Wire CH2 L L I Shielded cable *1 3-Wire Ni100Pt100,J P,t100, Cu50, C u100/ Ni1000, P t1000, LG-Ni1000 *3 1+ ADC 1- *2 INA 1- D A G 2+ 2- 2- A G L 1- I 1- SL D L L 2+ 2- I 2-