Chapter 6 Temperature Measurement Module AS04/06RTD 6. Channel Detection If an input signal exceeds the allowable range of inputs, an error message appears. You can disable this function so that the module does not produce an alarm or a warning when the input signal exceeds the input range. 7. Limit Detections for Channels This function saves the maximum and minimum values for channels so that you can determine the peak to peak values. Value of the channel Maximum value Minimum value Time 8. Records for Channels Record the input values of the cyclic sampling for each channel.
The system saves up to 500 data points for AS04RTD-A and up to 200 data points for AS06RTD-A and the recording time is 100 ms. The following uses AS04RTD-A as an example to demonstrate. 6_ Value of the channel 500 records of data Instruction for recording Recording ends Time 9. PID control PID algorithm is available for every channel. With its auto tuning function, parameters such as Kp, Ki, Kd and more can be calculated and therefore temperature control can be achieved. You can also use DMPID instruction to calculate relative parameters by entering the parameters in the endpoints of corresponding instruction image and you can then obtain the output values from the output endpoints. Note:
DMPID instruction is availbe for AS04RTD-A (V1.04 or later), AS06RTD-A (V1.00 or later), AS Series PLC (V1.06 or later) and AS-SCM (V2.04 or later). 6-17