AS Series Module Manual _7 7-24 Operand Data type Function Setting range Description present error meets the cross status The error value (E) is the difference between the SV and the PV. When the ERR DBW _ setting value is 0, the function is disabled; otherwise the CPU PLC checks whether the present error is less than the absolute value of ERR DBW, and _ checks whether the present error meets the cross status condition. If the present error is less than the absolute value of ERR DBW, _ and meets the cross status condition, the present error is counted as 0, and the PLC applies the PID algorithm ; otherwise the present error is brought into the PID algorithm.