Delta Electronics — 7.2.7 Control Mode

Chapter 7 Temperature Measurement Module AS04/08TC 7_ 7-23 Operand Data type Function Setting range Description Tf REAL Derivate-action time constant Range of positive single- precision floating- point numbers (unit: sec) If the derivate- action time constant is less than 0, Tf is 0 and it is not controlled by the derivate-action time constant (derivative smoothing). PID EQ _ BOOL PID formula types True: dependent formula False: independent formula PID DE _ BOOL The calculation of the PID derivative error True: use the variations in the PV to calculate the control value of the derivative (Derivative of the PV). False:

use the variations in the error (E) to calculate the control value of the derivative (derivative of the error). PID DIR _ BOOL PID forward/reverse direction True: reverse action; heating up (E=SV-PV) False: forward action; cooling down (E=PV-SV) ERR DBW _ DWORD/DINT Range within which the error value is counted as 0. -32768~32767 The error value (E) is the difference between the SV and the PV. When the setting value is 0, the function disabled; otherwise the CPU module checks whether the present error is less than the absolute value of ERR DBW, and _ checks whether the