Delta Electronics — 8.2.4 Control Registers

Chapter 8 Load Cell Module AS02LC 8.2.4 Control Registers *If you use HWCONFIG to set values in CRs, once the set value is downloaded, the values can be retained in the module; however if you use TO instruction to write data into CRs, the values CANNOT be retained, after power failure or after transition of the CPU from STOP to RUN. Note: The attribute of the CR must be W (write) to use TO instruction. 8_ 8-5 CR# Name Description Att. Default 0 Display options for CH1 0: disabled 1: gross weight 2: net weight 3: raw data R/W 1 1 Eigenvalue for CH1 0: 1 mV/V 1: 2 mV/V 2: 4 mV/V 3: 6 mV/V 4: 20 mV/V 5: 40 mV/V 6: 80 mV/V R/W 1 2 Sampling cycle for CH1 0: 2.5ms 1: 10ms 2: 16ms 3: 20ms 4:

50ms 5: 60ms 6: 100ms 7: 200ms 8: 400ms R/W 4 3 Weight measured times in a stability range for CH1 Range: K1–K500 R/W 5 4 Stability range for CH1 Floating-point format Range: 0–100000 R/W 10 5 6 Maximum weight for CH1 Floating-point format Maximum measuring weight; when the R/W 100,000