Delta Electronics — 9.4.2.4 Connecting to 3rd Party PLC Scanner through EIP Builder

Chapter 9 Serial Communication Module AS00SCM 5. Analog module: Refer to the following table to enter the corresponding instances in the fields. The following example shows AS04AD-A is installed in I/O 2. And according to the table below, you need to enter the value 105 in the field of input and 104 in the field of output in the Remote Data section. As for the data size, enter 10 for the input and 0 for the output. The unit is REAL. 9_ 9-33 I/O 1 I/O 2 I/O 3 I/O 4 I/O 5 I/O 6 I/O 7 I/O 8 Input 103 105 107 109 111 113 115 117 Output 102 104 106 108 110 112 114 116 Analog I/O Module I/O Data Size (Unit:

REAL) ASRTU-FEN02 → EtherNet/IP Scanner EtherNet/IP Scanner → ASRTU-FEN02 (Input) (Output) AS04AD-A 10 0 AS08AD-B 10 0 AS08AD-C 10 0 AS04DA-A 1 9 AS06XA-A 5 5 AS04RTD-A 10 0 AS06RTD-A 10 0 AS04TC-A 10 0 AS08TC-A 10 0