Chapter 9 Serial Communication Module AS00SCM 9.5 Normal Exchange Area 1) COM mode In the examples above, note that the Normal Exchange Area shows the corresponding data registers of the module and the PLC. Module Status: 0 = stop, 1 = run Error Code: refer to Section 9.7 for more information. Card 1 & Card 2 Data Exchange State: occupies 4 data registers (32-bit data); each bit 1–32 represents the 9_ state of the corresponding data point 1–32 to be exchanged: 0 = none/fail, 1 = success. Card 1 & Card 2 Data Exchange Mode Control: set the data register to 0: none, 1: once, 2: always. Card 1 & Card 2 Data Exchange Trigger:
occupies 4 data registers; each bit 1–32 represents the state of the corresponding data point 1–32 to be exchanged: 0 = no trigger, 1 = trigger. Card 1 & Card 2 UD Link Group ID Trigger: set the group ID to be triggered. 9-37