Chapter 10 Function Cards 10.2.7.3 Specifications System Specifications MODBUS TCP Specifications (only available for CPU modules) EtherNet/IP Specifications 10 10-7 Item Specification General Device type Master, Slave and RTU Topology Star and linear topologies are supported. IP Settings When installed on AS300 PLC CPU, you can only use HWCONFIG from ISPSoft for editing. When installed on AS00SCM-A and used for RTU application, you can edit via software or hardware. Software: Set the ID2 and FORMAT2 to 0x000 and use HWCONFIG from EIP Builder for editing. Hardware:
Use the ID2 and FORMAT2 to set IP address to 192.168.1.X (X=1~254) or turn ID2 and FORMAT2 to 0xFF to make it in DHCP mode. Availability AS300 Series PLC AS00SCM-A (available only for RTU mode) Web Max. connection number 8 Functions View device information Account management AS-FEN02 firmware update When installed in AS00SCM-A and in RTU mode, the module monitoring is supported. Item Specification General Device type Server, Client MODBUS TCP Server Max. connection number 8 Max. data length/per transmission 200 words MODBUS TCP Client Max. connection number 8 Max. data length/per transmission 200 words Note: The connection numbers of Server and Client are counted separately.
Item Specification General Device type Adapter CIP Network I/O Connection CIP connection number 8 TCP connection number 8 (Servers) Requested Packet Interval (RPI) 1 ms~1000ms Max. Transmission Speed 10,000 pps Max. data length/per transmission 200 bytes CIP Network Explicit Message Class 3 (Connected Type) Total 8 (Servers) (for both class 3 and UCMM connection types) UCMM