Delta Electronics — 10.2.7.3 Specifications

Chapter 10 Function Cards 10.2.7.3 Specifications  System Specifications  MODBUS TCP Specifications (only available for CPU modules)  EtherNet/IP Specifications 10 10-7 Item Specification General Device type Master, Slave and RTU Topology Star and linear topologies are supported. IP Settings  When installed on AS300 PLC CPU, you can only use HWCONFIG from ISPSoft for editing.  When installed on AS00SCM-A and used for RTU application, you can edit via software or hardware.  Software: Set the ID2 and FORMAT2 to 0x000 and use HWCONFIG from EIP Builder for editing.  Hardware:

Use the ID2 and FORMAT2 to set IP address to 192.168.1.X (X=1~254) or turn ID2 and FORMAT2 to 0xFF to make it in DHCP mode. Availability AS300 Series PLC AS00SCM-A (available only for RTU mode) Web Max. connection number 8 Functions View device information Account management AS-FEN02 firmware update When installed in AS00SCM-A and in RTU mode, the module monitoring is supported. Item Specification General Device type Server, Client MODBUS TCP Server Max. connection number 8 Max. data length/per transmission 200 words MODBUS TCP Client Max. connection number 8 Max. data length/per transmission 200 words Note: The connection numbers of Server and Client are counted separately.

Item Specification General Device type Adapter CIP Network I/O Connection CIP connection number 8 TCP connection number 8 (Servers) Requested Packet Interval (RPI) 1 ms~1000ms Max. Transmission Speed 10,000 pps Max. data length/per transmission 200 bytes CIP Network Explicit Message Class 3 (Connected Type) Total 8 (Servers) (for both class 3 and UCMM connection types) UCMM