Delta Electronics — 10.2.7.2 Features

AS Series Module Manual 10.2.7 AS-FEN02 This communication card can work independently and does NOT occupy the communication port of PLC CPU. It can act as Modbus TCP Server or Client and EtherNet/IP Adapter. After AS-FEN02 is installed, you can go to HWCONFIG from ISPSoft to do the editing in the Function Card 2 section. All the AS-FEN02 parameters are stored in AS300 PLC CPU or AS00SCM-A. If you need the IP address of AS-FEN02, you need to go to HWCONFIG from ISPSoft to check its IP address in the Function Card 2 section. You can also use COMMGR to see the IP address of this device.

10.2.7.1 Supported Software and Firmware Versions  The firmware of AS300 Series PLC should be V1.06 or later for AS-FEN02 to be installed on it.  The firmware of AS00SCM-A module (in RTU mode) should be V2.02 or later for AS-FEN02 to be installed on it.  ISPSoft version should be V3.06 or later.  EIP Builder version should be V1.06 or later. 10.2.7.2 Features  AS-FEN02 can be installed on AS300 Series PLC and AS00SCM-A (in RTU mode). This section introduces the operations when it is installed on AS300 Series PLC. For the operations when it is installed on AS00SCM-A and acting as remote module for AS/AH Series PLC, refer to section 9.4.2 for more details.

 When AS-FEN02 is installed on AS300 Series PLC, it acts as a Master or a Slave for Modbus TCP connection. The operation is the same as using the built-in connection port for communication and select FEN02 as the Function Card on Data Exchange tab, refer to section 9.3.1.2 of AS Series Operation Manual for more details.  When AS-FEN02 is installed on AS300 Series PLC, it acts as a EthernNet/IP Adapter but not EtherNet/IP 10 Scanner for EtherNet/IP connection. The operation is the same as the EtherNet/IP port on AS Series PLC, refer to Section 10.2.7.6 in this manual and Chapter 9 of AS Series Operation Manual for more details. 10-6