Chapter 10 Function Cards 10.2.5 AS-F2DA 2 DC analog signal output channels: *1: The conversion time is the time for each channel to convert signals to hardware input signals. If you need to calculate a complete conversion time, you need to add the PLC scan time. *2: Use the MOV instruction to move the value to the SR to obtain the corresponding voltage output value. 10.2.6 AS-FCOPM With its own standalone communication port, the AS-FCOPM card can work independently and can be either a slave or a master node. After installing the extension card, use HWCONFIG in ISPSoft to configure the communication.
Wiring example 10 10-5 Item Voltage Output Current Output Analog Signal 0 V - 10 V 4 mA - 20 mA Resolution 12-bit 12-bit Digital Conversion Limit 0 - 4000 0 - 4000 Error Rate room temperature: ±0.5% ; full temperature range:
±1.0% Impedance Allowance ≥1 kΩ ≤500 Ω Conversion Time*1 2ms / CH Characteristic Curve 10V Output Voltage 0 4000 Digital Value Input 20mA Output Current 4 4000 Digital Value Input Digital Value Output*2 Card 1 SR172 (CH1) SR173 (CH2) Card 2 SR174 (CH1) SR175 (CH2) Master node Slave node Slave node CAN _H CAN _LGND CAN _H C AN _LG ND GN D C AN _H C AN_ L Terminal Terminal resistor Shielded resistor (120 ohm) cable (120 ohm) ON 120 OFF Master node Slave node Slave node CAN _H CAN _LGND CAN _H C AN _LG ND GN D C AN _H C AN_ L Terminal Terminal resistor Shielded resistor (120 ohm) cable (120 ohm) CAN _H CAN _L GND CAN _H C AN _L Shielded cable C AN _H C AN_ L