Delta Electronics — 10.2.4 AS-F2AD

AS Series Module Manual 10.2.4 AS-F2AD 2 DC analog signal input channels: *1: The input signal should NOT exceed the limit. If exceeding the limit, damage may occur. *2: If the input signal exceeds the hardware input limit, the module only shows the maximum value. If the input signal is below the lower limit, it only shows the minimum value. If the input signal exceeds the hardware input limit, it also exceeds the digital conversion limit and a conversion limit error appears. For example in the current input mode (4 mA to 20 mA), when the input signal is 0 mA, exceeding the hardware lower limit, it also exceeds the conversion lower limit.

The module uses the lower limit value (-48) as the input signal. If a disconnected analysis is required, you can check if the digital conversion value is -48. *3: The conversion time is the time for each channel to convert signals to hardware input signals. If you need to calculate a complete conversion time, you need to add the PLC scan time. *4: Use the program to read the values in SR to obtain the corresponding A/D conversion value for the channel.

10 10-4 Item Voltage Input Current Input Rated Input Range 0 V - 10 V 4 mA - 20 mA Resolution 12-bit 11-bit Digital Conversion Range 0 - 4000 0 - 2000 Hardware Input Limit*1 0V ~ +10.24V 4mA ~ 20.37mA (FW V1.00) 3.63mA ~ 20.37mA (FW V1.20 or later) Digital Conversion Limit*2 0 ~ 4095 0 ~ 2047 (FW V1.00) - 48 ~ 2047(FW V1.20 or later) Error Rate room temperature: ±0.5% ; full temperature range: ±1.0% Input Impedance 2 MΩ 250 Ω Conversion Time*3 3 ms / CH Characteristic Curve 4000 Output Value Digital 0 10V Voltage input 2000 Output Value Digital 4 20mA Current input Digital Value Output*4 Card 1 SR168 (CH1), SR169 (CH2) Card 2 SR170 (CH1), SR171 (CH2)