AS Series Module Manual 10.2.7.8 Data Mapping through Modbus TCP When AS-FEN02 is installed on AS Series PLC, you can create a connection by configuring the IP address and some relevant parameters to make it act as a Modbus TCP Slave device. the other as Slave (AS-FEN02) to perform data mapping through the Modbus TCP connection. For the support function The following example shows two AS Series PLCs (one with AS-FEN02) to connect each other and one as Master and codes and corresponding addresses, refer to AS Series Operation Manual for more details. Step 1 Double click AS Series PLC in HWCONFIG and the Device Setting window appears.
Set up the IP Address of the A to 192.168.1.3 and then connect Master and Slave AS-FEN02. Step 2 Create a data mapping table in the Master and then perform data mapping with the Slave (AS-FEN02). 10 10-18 Device Function IP Address Data Mapping Area AS300 Modbus TCP Master 192.168.1.5 D100, D200 AS300+ AS-FEN02 Modbus TCP Slave 192.168.1.3 D200, D300