Delta Electronics — 10.2.7.7 Example of Connecting to 3rd Party PLC Scanner through EIP Builder

Chapter 10 Function Cards 10 10-17 I/O Message Connection Instance Connection No. Function Length Defaults Attribute Connection 6 Input (TO) 0x6F 100 words D3500~D3599 Output (OT) 0x6E 100 words D2500~D2599 Configuration 0x85 8 words Refer to the table below Connection 7 Input (TO) 0x71 100 words D3600~D3699 Output (OT) 0x70 100 words D2600~D2699 Configuration 0x86 8 words Refer to the table below Connection 8 Input (TO) 0x73 100 words D3700~D3799 Output (OT) 0x72 100 words D2700~D2799 Configuration 0x87 8 words Refer to the table below Configuration address Data type Description Defaults (Connection 1) Word[0] UINT Input corresponding device 0: D, 1: X, 2:

Y 0 Word[1] UINT Reserved 200 Word[2-3] DWORD Input corresponding device number 3000 Word[4] UINT Output corresponding device 0: D, 2: Y 0 Word[5] UINT Reserved 200 Word[6-7] DWORD Output corresponding device number 2000