Delta Electronics — 10.2.8.4 LED Indicators

AS Series Module Manual 10.2.8.3 Specifications 10.2.8.4 LED Indicators RJ-45 Pin Definition 1 TX+ 2 TX- 3 RX+ 4 N/C 5 N/C 6 RX- 7 N/C 8 N/C 10 10-24 Item Specification Installed on PLC AS300 AS00SCM Communication Protocol PROFINET RT EtherNet/IP Interface 100 Mbit with 2 x RJ45 Fieldbus PROFINET Devices Network Cable Length 100 meter Error Indicator System Fail (SF): Red; Bus Fail (BF): Red Max. IO Slot Supported 17 9 Devices to Read and Write AS300 series data registers RTU modules Minimum Time for Data Exchange to Operate 10 ms Maximum Data Length/Per Transmission Input: 250 words Output:

250 words PROFINET Configuration Download PROFINET Configurations from PN Controller Number Name Description System Fault Indicator RED light ON: an error occurs in PROFINET configuration or incorrect 1 SF indicator data for exchange OFF: no system error Bus Fault Indicator RED light ON: the network connection is OFF. 2 BF indicator RED light BLINKING: the network connection is working fine but the communication with PN Controller is NOT normal. OFF: the communication with PN Controller is working fine. Indicates the status of Ethernet connection 3 LINK indicator X1/X2 Green light ON: a network connection is established OFF:

a network connection is not established Indicates the status of Ethernet communication 4 ACT indicator X1/X2 Orange BLINKING: data transmission OFF: no data transmission