Delta Electronics — 10.2.8.5 Configuring the Data Length for I/O Module (Works with AS300)

Chapter 10 Function Cards 10.2.8.5 Configuring the Data Length for I/O Module (Works with AS300) available. You can use PN Controller’s Software (the example below uses Siemens TIA Portal software) to configure the When AS-FPFN02 communication card is installed on AS300 Series PLC, up to 500/500 bytes of I/O address area are modules and set up the data size for data exchange. You can also set up the corresponding I/O module addresses to the AS300 data register addresses. Refer to Section 10.2.8.10 for more reference. The total data size and the number of modules used are relevant.

The total usage of I/O address area should also include Device Access Point (DAP) and the bytes for information, such as IO Production Status (IOPS) and IO Consumption Status (IOCS) of each module. 10 10-25 Module Type Data Length (for both DIO and AIO modules) (IOPS & IOCS) Slot 0 (DAP) 4 bytes Input module 1 byte Output module 1 byte I/O module 2 bytes