AS Series Module Manual Example: The address area used is within 500/500 bytes. But you need to add bytes used on IO Production Status (IOPS) and IO Consumption Status (IOCS) of each module too. Here the example shows the address area of the input module is taken by 500 bytes (data length) + 4 bytes (Slot 0) + 2 bytes *7 (7 I/O modules) + 1 byte (Slot 1) = 519 bytes. The same example shows that the address area of the output module is taken by 500 bytes (data length) + 4 bytes (Slot 0) + 2 bytes *7 (7 I/O modules) + 1 byte (Slot 9) = 519 bytes. The data exceeds the total permitted maximum data length of 500/500 bytes. An error message appears as the image shown below by TIA Portal. Note: