Delta Electronics — 11.2.4 DeviceNet Connector

Chapter 11 DeviceNet Master Scanner Module AS01DNET-A 11.2.2 Components 1 2 11 3 4 5 6 RTU Master Slave / Note : The power input port of the network module is required to connect an external 24VDC power supply only when the toggle (RTU- Master/Slave) is switched to RTU mode. Otherwise, the port does not need an external 24VDC power supply connected when the toggle (RTU- Master/Slave) is switched to Master/Slave mode. 11.2.3 Mode Toggle ( RTU- Master/Slave ) 11.2.4 DeviceNet Connector The connector is used for the connection to DeviceNet. Wire by using the connector enclosed with AS01DNET –A.

11-5 7 8 01D I I x101 N 0 N 1 Node Ad x100 9 10 ① Model name ⑥ Mode toggle (RTU-Master/Slave) ② State indicators ⑦ Left-side extension port ③ Address switch ⑧ Nameplate ④ Function switch ⑨ Right-side extension port ⑤ DeviceNet communication port ⑩ 24V DC power input port for RTU mode RTU M a ste r/ Sl ave Mode Selection Description Master/Slave Works in master or slave mode and constitutes a DeviceNet master or slave without external power supply. RTU When working in remote (RTU) mode, AS01DNET-A is required to connect the external DC 24V power supply and can have AS series I/O modules connected on its right side.

Pin Signal Color Description 1 V- Black 0 VDC 2 CAN L _ Blue Signal- 3 SHIELD - Shielded wire 4 CAN H _ White Signal+ 5 V+ Red 24 VDC