AS Series Module Manual 11.2.5 Address Switch The switch is used for setting up the node address of AS01DNET-A in DeviceNet network. Range: 00~63 (64~99 11 are forbidden.) Example: If users need to set the node address of AS01DNET-A to 26, simply switch the corresponding switch of x101 to 2 and the corresponding switch of x100 to 6. Note: After the setup is completed, repower AS01DNET-A. While AS01DNET-A is working, changing the setting of the node address is invalid. Rotate the switch carefully with a slotted screwdriver to prevent damage to the switch. 11.2.6 Function Switch The function switches are used for:
Setting up the work mode (IN0) Setting up the baud rate of DeviceNet network (DR0~DR1) Note: After the setup of the function switch is completed during power off, repower AS01DNET-A. While AS01DNET-A is working, changing the setting of the node address is invalid. Adjust the DIP switch carefully with a slotted screwdriver to prevent any damage to the switch. 11.2.7 Digital Displayer The digital displayer provides following functions: Showing the node address of AS01DNET-A and error ID Showing the error information about a slave 11-6 2 3 1 4 x101 0 5 9 6 8 7 Node Address 2 3 1 4 x100 0 5 9 6 8 7 Switch setting Description 0 …
63 Valid DeviceNet node address 64…99 Invalid DeviceNet node address DR1 DR0 Baud Rate IN 0 IN 1 OFF OFF 125 Kbps OFF ON 250 Kbps ON OFF 500 Kbps ON ON Entering the mode of extended baud rate IN0 ON When the slave is off-line, the I/O data in the buffer area will be held. OFF When the slave is off-line, the I/O data in the buffer area will be cleared. IN1 Reserved 01DNET