Delta Electronics — 11.4.6 Setting the Time for Data Exchange between Master and Slaves

AS Series Module Manual 11.4.5 Network Node Status Display 11.4.5.1. Scan-List Node Status Indication 11 The following table takes the first AS01DNET on the right of AS PLC for example. AS01DNET master can monitor whether the configured slave is online or not in real time and have the status of the configured slave mapped to one bit. Users can get the status of network nodes by monitoring the contents in D26000~D26003. The corresponding relationships between devices in the PLC and network nodes are shown in the following table. If the node in Scan List is normal, the corresponding bit is OFF. If the node in Scan List is abnormal, the corresponding bit is ON. 11.4.5.2.

Module Status Indication The following table takes the first AS01DNET on the right of AS PLC for example. Users can get the status of the network is initializing, the content in the high byte of D26004 is 1 and the content in the low byte is 0. When an error occurs in the node by monitoring the content in D26004. When the module works normally, the content in D26004 is 0. When the module module, the content in the high byte of D26004 is 2 and the content in the low byte is an error code. For details on error codes, see Digital Displayer. 11.4.6 Setting the Time for Data Exchange between Master and Slaves set.

Master and all salves will periodically perform the data exchange based on the set time. See the following explanation When AS01DNET works in master mode, the period of time for a data exchange between master and all slaves need be for details. Click menu Network >> Scanner Setting on the DeviceNet Builder software page. The Scanner Setting window appears as below. 11-18 Register in Corresponding network node the PLC b15 b14 b13 … … b1 b0 D26000 Node15 Node 14 Node 13 … … Node 1 Node 0 D26001 Node 31 Node 30 Node 29 … … Node 17 Node 16 D26002 Node 47 Node 46 Node 45 … … Node 33 Node 32 D26003 Node 63 Node 62 Node 61 … …

Node 49 Node 48 Register in Description the PLC b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 D26004 Module status (0:Normal,1:Initializing,2:error) Error code in the module