Delta Electronics — 11.4.7.3. DeviceNet Network Control

AS Series Module Manual  Configure the DeviceNet network by following the steps above. The IO data mappings between AS01DNET-A and the slave are shown in the following tables. 11  AS01DNET-A → Slave  Slave → AS01DNET-A  Saving configuration data Select File >> Save to save current network configuration. 11.4.7.3. DeviceNet Network Control This section describes how to write a ladder program to achieve the control requirement of the DeviceNet network.  PLC Programs  The program in the PLC connecting AS01DNET slave: Program Explanation: The contents in D26000~D26003 are the data received from the master and the contents in D26100~D26103 are the data transmitted to the master.

SM400 is a normally open contact. The program above can make the contents in D26000~D26003 move to D26100~D26103.  The program in the PLC connecting AS01DNET master: 11-28 AS PLC AS01DNET(Master) AS01DNET(Slave) AS PLC D26105 D26000 D26106 D26001 D26107 D26002 D26108 D26003 AS PLC AS01DNET(Master) AS01DNET(Slave) AS PLC D26005 D26100 D26006 D26101 D26007 D26102 D26008 D26103