Chapter 11 DeviceNet Master Scanner Module AS01DNET-A  PLC Program 11  S1 : The number of the module sending DeviceNet communication. The first one of the right side is 01.  S2 : DeviceNet node ID (MAC ID); Node ID of VFD-C2000: 00.  S3 : Service code; 0X10: read one single attribute content.  S4 : Class ID; Class ID of CMC-DN01: 05.  S5 : Instance ID; Instance ID of CMC-DN01: 01.  S6 : Attribute ID; Attribute ID of CMC-DN01: 09.  S7 : Write data size with the unit: Byte. The written-data size is 2 in this example.  S8 : The start device where the written data are stored.  S9 : Communication timeout time.  S10 : Times of re-transmission.

Times of re-sending communication when communication timeout occurs.  D1 : Completion flag.  D2 : Error flag.  D3 : Error code.  D4 : Read data size. When DNETRW instruction is used to write data, the value in D4 can be set to any data.  D5 : The start device where read data are stored. When DNETRW instruction is used to write data, the value in D5 can be set to any data. 11-35