Delta Electronics — 11.4.9.1. NS LED

AS Series Module Manual  Program Explanation  When M0 changes to ON, AS01DNET-A sends the request message and 000AHex is written to Class 11 ID: 05>> Instance 1 >> Attribute ID: 09 of the target equipment with node ID: 01. If explicit message communication succeeds, the completion flag M1 changes to ON.  When M0 changes to ON, AS01DNET-A sends out the request message only once. If the request message is to be resent, the instruction DNETRW need be re-triggered. 11.4.9 LED Indicators and Troubleshooting AS01DNET-A has two LED indicators and one digital displayer. NS LED and MS LED display the connection status of information of the slave. AS01DNET-A.

The digital displayer shows the node address and error information of AS01DNET-A as well as error 11.4.9.1. NS LED 11-36 01DNET LED status Indication Correction OFF No power; Or duplicate ID check has not been completed. 1. Check if AS01DNET-A is powered and the connection is normal. 2. Make sure that at least one node can communicate normally. Green light blinking (ON:0.5s and OFF: 0.5s alternately) The connection to the DeviceNet network failed. No correction; Refer to Digital Displayer for troubleshooting. Green light ON Online; The connection to the DeviceNet network is normal. No correction Red light blinking (ON:0.5s and OFF:

0.5s alternately) Communication error Refer to Digital Displayer for troubleshooting. Red light ON Network trouble, duplicate node ID, no network power or Bus-OFF. 1. Make sure that all the devices in the network have their unique node addresses. 2. Check if the network installation is correct. 3. Check if the baud rates of the master and slave are same. 4. Check if the network power is normal.