AS Series Module Manual 11.5.2 AS-Series Extension Modules Connectable to AS01DNET (RTU) The model and specification of AS-series digital modules connectable to AS01DNET (in RTU mode): 11 The model and specification of AS-series special modules connectable to AS01DNET (in RTU mode): Note: The length of mapping data of the I/O modules connected to AS01DNET (in RTU mode) is fixed. The default mapping parameters of special modules must be chosen. Besides default mapping parameter configuration, you can also choose other parameters for I/O mapping according to need when special modules are connected to AS01DNET (RTU). The max. input length and max.
output length of default parameters and user-added mapping parameters of each special module are both 20 words. 11-52 Digital I/O module model Length of I/O mapping data (Unit: words) (Master→AS01DNET) (AS01DNET→Master) AS08AM10N-A None 1 AS16AM10N-A None 1 AS32AM10N-A None 2 AS64AM10N-A None 4 AS08AN01T-A 1 None AS08AN01R-A 1 None AS08AN01P-A 1 None AS16AN01T-A 1 None AS16AN01R-A 1 None AS16AN01P-A 1 None AS32AN02T-A 2 None AS64AN02T-A 4 None AS16AP11T-A 1 1 AS16AP11R-A 1 1 AS16AP11P-A 1 1 Special module model Length of I/O mapping data (Unit:
words) DeviceNet→AS01DNET(RTU) AS01DNET(RTU)→DeviceNet AS04AD-A 6 None AS04DA-A 2 4 AS06XA-A 10 4 AS02LC-A 7 1 AS04RTD-A 10 None AS06RTD-A 14 None AS04TC-A 10 None AS08TC-A 18 None AS08AD-B 18 None AS08AD-C 18 None