AS Series Module Manual 11.5.4.3.4. Status Word and Control Word of AS01DNET (RTU) and control word of AS01DNET (RTU) respectively with the detailed explanation in the following table.
The start input address and start output address in the mapping areas of AS01DNET (RTU) are used as the status word 11 Control word of AS01DNET(RTU) Status word of AS01DNET(RTU) 11-80 Bit Status value Description bit0 ~ bit2 000 Make no control setting for the operation of AS01DNET(RTU) 001 Set AS01DNET(RTU) to RUN mode 010 Set AS01DNET(RTU) to STOP mode Other Reserved bit3 0 Reserved 1 Restart AS01DNET (RTU) bit4 0/1 Reserved bit5 0/1 Reserved bit6 0/1 Reserved bit7 0/1 Reserved bit8 0/1 Reserved bit9 0/1 Reserved bit10 0/1 Reserved bit11 0/1 Reserved bit12 0/1 Reserved bit13 0/1 Reserved bit14 0/1 Reserved bit15 0/1 Reserved Bit Status value Description bit0 0 AS01DNET (RTU) in RUN state 1 AS01DNET (RTU) stops.
bit1 0/1 Reserved bit2 0 No error occurs in I/O modules. 1 An error occurs in I/O modules. bit3 0/1 Reserved bit4 0 Current connection matches the configuration. 1 Current connection is inconsistent with the configuration. bit5 0 AS01DNET (RTU) works normally. 1 The voltage of the power supply for AS01DNET (RTU) is too low. bit6 0/1 Reserved bit7 0 AS01DNET (RTU) works normally. 1 The number of points/ modules exceeds allowed range. bit8 0/1 Reserved bit9 0/1 Reserved bit10 0/1 Reserved bit11 0/1 Reserved bit12 0/1 Reserved