Delta Electronics — 11.5.4.4. Connecting AS01DNET (RTU) to the Network

Chapter 11 DeviceNet Master Scanner Module AS01DNET-A 11 11.5.4.4. Connecting AS01DNET (RTU) to the Network To configure AS01DNET (RTU) successfully and make it work normally in the network, the following steps should be taken for the setup. Ha rdwa re Wiri ng Moni tor & Che ck Configurati on Setting  Hardware wiring During hardware wiring, notice that the standard cable should be used and two terminal resistors of 121Ω should be connected respectively to the two ends of the main line in the DeviceNet network. The node IDs of all nodes in the network bus can not be repeated and their baud rates should be consistent.  Online scan The online scan consists of two parts:

scanning online network nodes and scanning I/O modules of AS01DNET (RTU). Before the scan, make sure that the communication channel selected is proper and the communication setup is normal in the communication manager COMMGR.  Configuration setting The configuration setting includes the master configuration and AS01DNET (RTU) configuration settings. The master AS01DNET (RTU) configuration contains AS01DNET (RTU) setting and other I/O modules setting. configuration contains the master scanner module setting (configuration of master) and the scan list configuration setting.

 Configuration Download Configuration download consists of master configuration download and AS01DNET (RTU) configuration download. During the master configuration download, the seven-segment displayer of AS01DNET (RTU) shows 80 and its node ID alternately. its node ID alternately. During the AS01DNET (RTU) configuration download, the seven-segment displayer of AS01DNET (RTU) shows 83 and  Monitor and Check After the configuration is downloaded, check if AS01DNET (RTU) works normally. If AS01DNET (RTU) works normally, the digital displayers of the master and AS01DNET (RTU) show their own node IDs and MS and NS indicators are ON in green.

11-81 Bit Status value Description bit13 0/1 Reserved bit14 0/1 Reserved bit15 0/1 Reserved Onli ne Scan Configurati on Download