AS Series Module Manual 11.5.6.1. Indicator Diagnosis NS indicator 11 MS indicator 11-92 LED status Indication How to deal with OFF No power supply; Or the repeated node ID detection has not been completed. 1. Check the power supply for AS01DNET (RTU) and the connection are normal. 2. Make sure that the baud rates of AS01DNET (RTU) and the master match. Green light blinking (ON:0.5s and OFF: 0.5s alternately) No connection between AS01DNET (RTU) and its right- side modules Configure AS01DNET (RTU) in the DeviceNet software and download the configuration correctly.
Green light ON Normal I/O data transmission between AS01DNET (RTU) and DeviceNet master No correction needed Red light blinking (ON:0.5s and OFF: 0.5s alternately) I/O connection timeout between AS01DNET (RTU) and DeviceNet master Refer to the error shooting in Codes in Seven-Segment Displayer below. Red light ON Network trouble; Repeated node ID; No network power; Or BUS-OFF. 1. Ensure that the IDs of all nodes are unique on the bus. 2. Check if the network installation is normal. 3. Check if the baud rate of AS01DNET (RTU) is the same as that of the bus. 4. Check if the node ID of AS01DNET (RTU) is valid. 5. Check if the network power supply is normal.
LED status Indication How to deal with OFF No power Check if the power supply for AS01DNET (RTU) and connection are normal. Green light blinking (ON:0.5s and OFF: 0.5s alternately) 1. AS01DNET (RTU) is waiting for the I/O data from DeviceNet master. 2. No I/O data transmission between AS01DNET(RTU) and DeviceNet master 3. The PLC connected to DeviceNet master is in STOP state. 1. Configure AS01DNET (RTU) in the DeviceNet software and download the configuration correctly. 2. Switch the PLC to RUN state Green light ON Normal transmission of I/O data between AS01DNET (RTU) and DeviceNet master No correction needed