Delta Electronics — 11.5.6.2. Codes in Seven-Segment Displayer

Chapter 11 DeviceNet Master Scanner Module AS01DNET-A 11 11.5.6.2. Codes in Seven-Segment Displayer 11-93 LED status Indication How to deal with Red light blinking (ON:0.5s and OFF: 0.5s alternately) No network power supply; Configuration error; Module alarms. 1. Check if the network power supply is normal; 2. Reset the internal parameters in AS01DNET (RTU); 3. Check if there is an error or alarm in the I/O modules connected to the right side of AS01DNET (RTU). Red light ON Hardware error Return the product to factory for repair if the error still exists after re-power on.

Code Indication How to deal with 0~63 Node ID of the scanner module (When in RUN state) No correction needed F0 The node ID is repeated or exceeds allowed range. 1. Ensure that the node ID of AS01DNET (RTU) is unique in the DeviceNet network within the range of 0~63. 2. Repower it on after changing the node ID. F1 No I/O module is configured to AS01DNET (RTU) in the DeviceNet Builder software. Add I/O modules in AS01DNET (RTU) in the DeviceNet Builder software and download the configuration data to AS01DNET (RTU) after the configuration is finished. F2 The work voltage of AS01DNET (RTU) is too low. Check if the power supply for AS01DNET (RTU) works normally.

F3 AS01DNET (RTU) enters the test mode. Repower AS01DNET (RTU). F4 AS01DNET (RTU) is the Bus- Off state. 1. Check if the network communication cable is normal and the shielded cable is grounded. 2. Ensure the baud rates of all network nodes are same. 3. Check if the two ends of the network are both connected with a 120Ω terminal resistor. 4. Repower the scanner module. F5 No network power supply for AS01DNET(RTU) 1. Check if the network cable is normal. 2. Check if the network power supply is normal.

(The external 24V DC network power supply is connected between red V+ and black V- of AS01DNET (RTU) .) F6 Internal error; An error in the internal storage units of AS01DNET (RTU) Return the product to factory for repair if the error still exists after re-power on. F7 Internal error; An error in the data exchange units of AS01DNET (RTU) Return the product to factory for repair if the error still exists after re-power on. F8 Manufacture error Return the product to factory for repair if the error still exists after re-power on.