Chapter 11 DeviceNet Master Scanner Module AS01DNET-A 80 means AS01DNET (RTU) is in STOP state. 02 is the node ID: 2 of AS01DNET (RTU). 11.5.6.3. Status Word Diagnosis 11 following table for status word diagnosis and disposal. The status word of AS01DNET (RTU) shows the operation states of special modules and digital I/O modules. See the 11-95 Bit Status Description Disposal value bit0 0 AS01DNET (RTU) is in RUN state No correction needed 1 AS01DNET (RTU) is in STOP state.
Restart AS01DNET(RTU) bit1 0 Valid configuration data in AS01DNET(RTU) No correction needed 1 Invalid configuration data in AS01DNET (RTU) Re-download the configuration data to AS01DNET (RTU) by using the DeviceNet Builder software. bit2 Reserved —— —— bit3 Reserved —— —— bit4 0 Currently connected module matches the configuration in the software. No correction needed 1 Currently connected module is inconsistent with the configuration in the software. 1. Check if currently connected module is consistent with the configuration in the software. 2. Change current module to match the configuration in the software or change the configuration in the software to match currently connected module.
bit5 0 AS01DNET(RTU) in normal operation No correction needed 1 AS01DNET(RTU) in low voltage Check if the power supply for AS01DNET (RTU) is normal. bit6 Reserved —— —— bit7 0 AS01DNET(RTU) in normal operation No correction needed Reserved —— —— bit8 Reserved —— —— bit9 Reserved —— —— bit10 Reserved —— —— bit11 Reserved —— —— bit12 Reserved —— —— bit13 Reserved —— —— bit14 Reserved —— —— bit15 Reserved —— ——