AS Series Module Manual 11.5.6.4. Software Diagnosis follows. Click the Start Monitor button on the AS01DNET (RTU) interface. The Error code column will show relevant contents as 11 Note : For details on more error codes, refer to the explanation of Error ID in AS-series product manual. Remark: The software diagnosis function can not be enabled until the DeviceNet Builder software is online. 11-96 Error No. Explanation Solution 0x8001 AS01DNET (RTU) can not detect the configured module. 1. Check if the module is disconnected. 2. Check if the module is damaged. 0x8002 Current module is not consistent with the configured module.
Ensure that the actually connected module is the same as that configured in the software.