Delta Electronics — 13.2.2 Profile

AS Series Module Manual 13.2.2 Profile _13 Unit: mm 13-6 38.2 4 SI L L1+ P L1- L2+ MS NS L2- C1 95 1 7 WR 2 3 4 5 6 75 0 CQ 1 DI 1 CQ2 8 DI2 8 CQ3 DI3 CQ4 DI4 ● L3+ Q E1 1 L3 - QC 22 L4+ E2 L4- QC 33 24 V E3 C4 0V Q4 E4 7 8 Number Name Description 1 Model name Model name of the module Indicates the status of the power supply POWER LED indicator (Blue) ON: the power is on OFF: no power or the power voltage is too low Error status of the module OFF: The module is normal. Module LED indicator ON: The communication with its left-side PLC or RTU module fails. (Red) Blinking: 1. Module setting or communication error (blinks every 1 second) 2.

Hardware or low voltage error (blinks every 0.2 second) Error status of the network ON: No external power supply Network LED indicator Blinking: Scanning is ongoing or the module is already configured and (Orange) the diagnosis is done. OFF: The module has been configured but the diagnosis has not done yet. 2 IO-Link connection status of each communication port ON: The communication port is in IO-Link mode and a device is C1, C2, C3, C4 LED indicator connected. (Orange) Blinking: The communication port is in IO-Link mode but no device is connected or the device connected is not configured. OFF: The communication port is disabled or in SIO mode.

Indicates the status of input / output in SIO mode Q1, Q2, Q3, Q4 LED indicator ON: The input/output is working in SIO mode. (Orange) OFF: The communication port is disabled or in IO-Link mode. Indicates if any warning or error occurs in each communication port of E1, E2, E3, E4 LED indicator the IO-Link connection. (red) Blinking: A warning or an error occurs OFF: No warnings or errors 3 Removable terminal block IO-Link