Chapter 13 IO-Link Communication Module AS04SIL 13.2.3 Wiring 13.2.3.1 IO-Link Mode Wiring for Power and Communication Precautions: 1. Keep the input cables, output cables and power cable separate from one another. It is suggested to use independent 13 power for AS04SIL-A. See the example below. IO-Link Sensor (with DI) 1 Brown 2 White 4 Black 3 Blue 1 Brown 4 Black 3 Blue IO-Link Sensor (without DI) 24V 0V DC Power Supply 24VDC 2. The 24 VDC cable should be twisted and connected to a module within a short distance. 3.
Do not bundle 110 VAC cable, 220 VAC cable, 24 VDC cable, the (high-voltage high-current) main circuit, and the I/O signal cable together and keep the power cables away from the earth cable. It is suggested that the distance between adjacent cables should be more than 100 millimeters. 4. Connect a cable with a diameter of 14 AWG or higher to ground. 5. Use single-wire cables or two-wire cables with a diameter of 20 AWG to 14 AWG. Only use copper conducting wires with a temperature rating of 60/75 ° C.
13-7 Number Name Description Arrangement of the input/output 4 Arrangement of the terminals terminals 5 Terminal block clip Removal of the terminal block 6 DIN rail clip Secures the module onto the DIN rail 7 Module connecting set Connects the modules 8 Label Nameplate IO-Link Master AS04SIL-A . CQ1 . L1+ DI1 . . L1- CQ2 L2+ DI2 L2- . CQ3 . L3+ DI3 . L3- CQ4 L4+ DI4 L4- . 24V 0V