Chapter 13 IO-Link Communication Module AS04SIL 13.4.5 Application of CANopen DS301 Mode In this example, the AS00SCM-A RTU module works with EDS V2.06. Please download the EDS from Delta official website and import the CANopen Builder software. The device list in the following example is the same as that in section12.4.3. 13 The CANopen Builder does not support the configuration of extension modules on the right of the AS00SCM-A module and connected IO-Link devices. HWCONFIG 4.0 software (see the example in section 13.4.3) and then switch back to the CANopen DS301 mode.
First make the connection in AS Special Remote mode, configure all extension modules and IO-Link devices in the Please complete the following setups before the AS00SCM-A module is powered on. 1. The AS-FCOPM card is inserted to AS00SCM-A via Card 2. (The 120 Ω terminal resistor is enabled.) 2. Use Delta standard cables to connect to AS CPU and the mode switch is turned to RTU mode. 3. Four switches are set to ID1: 0 / FORMAT1: 4 / ID2: 2 / FORMAT2 : 7 and the status is set to CANopen DS301 , node ID 2 and baud rate 1Mbps. 4. AS04SIL-A is connected on the right side of AS00SCM (RTU). Ensure that IO-Link devices are connected to the four ports according to the wiring in section 13.2.3.
Switch the power on after the AS-FCOPM card is inserted to AS332T-A via Card 2. (The 120 Ω terminal resistor is enabled.) Open the HWCONFIG 4.0 software, set up function card 2 for AS CPU and then download the settings as follows. 13-33 Model name Device type AS332T-A PLC AS00SCM-A RTU AS04SIL-A IO-Link Master AI-B100 3rd IO-Link Device E3S-DCP21-IL3 3rd IO-Link Device MAXREFDES27# 3rd IO-Link Device MAXREFDES36# 3rd IO-Link Device