Chapter 14 High Speed Counter Module AS02HC Z-Phase Function Setting AS02HC-A’s two channels which are with one input point CH1 Z and CH2 Z respectively should be configured in function by HWCONFIG before they are used to achieve the functions of counter reset, gate control, counter value capture and digital filtering.
14 14-19 Item name Setting Unit Default Phase-Z Function Setting Counter Reset, Counter Reset +Yno, Gate Control and Capture - Counter Reset Phase-Z Function Description Remark Counter Reset (Default) The counter is cleared (the counter value is reset to 0 and the counter status is cleared.) The counter value can not be cleared if the SSI input and the absolute-position counter type are selected. Counter Reset +Yno Same to Counter Reset above. Also clears the output points that are set by the DHCCMP comparison instruction or table comparison instruction DHCCMPT. The DHCCMP or DHCCMPT instruction is used.
Capture The counter value capture is triggered through the rising edge and falling edge of phase Z. The DHCCAP instruction is used. Gate control When phase Z is at low level, the counter’s counting pauses. When phase Z is at high level, the counter’s counting continues. Applicable to the pulse input only. Item name Setting Unit Default Filter time 0 ~ 200 100 us 0 (Disabled)