Chapter 14 High Speed Counter Module AS02HC Troubleshooting Procedure 14 14-33 Description Solution Counted result in the latched area is not retainable (major error) Counted data is lost. Switch the module power OFF and ON again. The error code is cleared by the system. Contact the factory if the problem persists. Module settings in the latched area is not retainable. (major error) Module setting data is lost. Switch the module power OFF and ON again. Download the HWCONFIG settings again to clear the error code. Contact the factory if the problem persists. Module setting error (major error) Check if the setting in HWCONFIG is consistent with the actual placement.
Contact the factory if the problem persists. Counter overflow / underflow on CH1 Check the counter result. If the alarm is not required, disable the alarm output function in HWCONFIG. Use any of the followings to clear the error code: clear, reset, preset the counter, restart the module, or execute DHCCNT instruction again. Counter overflow / underflow on CH2 Linear count exceeding the set upper/lower limit on CH1 Check the signal received by channel 1 and 2. Hardware counter is still counting; when the number is back within the range of the maximum to the minimum, the error code will be cleared.
Linear count exceeding the set upper/lower limit on CH2 The variation in relation to a SSI encoder position exceeding the limit on CH1 Check if there is any interruption and check the device specification to see if the offset setting is matching with the actual placement. The variation in relation to a SSI encoder position exceeding the limit on CH2 Abnormal SSI communication on CH1 Check the execution of DHCCNT instruction. If it is parity check, check if there is any interruption and check if the data format is correct. Check if the device wiring is secure, and if the encoder power supply is normal.
Abnormal SSI communication on CH2 SSI absolute position cross zero point on CH1 Check the SSI absolute encoder specification and modify the setting accordingly. If the alarm is not required, disable the alarm output function in HWCONFIG. Use any of the followings to clear the error code: clear, reset, preset the counter, restart the module, or execute DHCCNT instruction again. SSI absolute position cross zero point on CH2