AS Series Module Manual 4.2.3 Arrangement of Terminals AS04DA-A _4 4.2.4 Control Registers *If you use HWCONFIG to set values in CRs, once the set value is downloaded, the values can be retained in the module; however if you use TO instruction to write data into CRs, the values CANNOT be retained, after power failure or after transition of the CPU from STOP to RUN. Note: The attribute of the CR must be W (write) to use TO instruction. 4-6 04 VO1 IO1 AG SLD VO3 IO3 AG SLD VO2 PW IO2 AG ERR D A SLD VO4 IO4 AG SLD 24V 0V CR# Name Description Atr. Defaults 0 Format Setup 0: integer format 1: floating-point format R 0 1 Channel 1 mode setup 0: closed 1: -10 V to +10 V (default) 2: 0 V–10 V 3:
-5 V to +5 V 4: 0 V–5 V 5: 1 V–5 V 6: 0 mA–20 mA 7: 4 mA–20 mA R/W 1 2 Channel 2 mode setup R/W 3 Channel 3 mode setup R/W 4 Channel 4 mode setup R/W 5 Channel 1 offset Range: -32768 to +32767 R/W 0