AS Series Module Manual 5. Scale Range You can set the scale range when the format is floating-point. The analog output mode of a channel has a corresponding digital range. Digital values correspond to analog outputs sent by the module. For example, if the analog range is -10 V to +10 V, the digital range is -10.0 to +10.0, the HSP scale is 10.0, and the LSP scale is -10.0. The digital values -10.0 to +10.0 correspond to the analog values -10 V to +10 V, as the example below shows.
Analog value 10 V Rated output range _4 -10 V Digital value -10.0 Scale range 10.0 4.2.6 Wiring Precautions To ensure the digital-to-analog module functions well and reliably, the external wiring must prevent noise. (1) To prevent a surge and induction, the AC cable and the output signal cables that are connected to the AS04DA-A must be separate cables. (2) Do not install or bound the cable to a main circuit, a high-voltage cable, or a cable connected to a load that is not a PLC. (3) Ground shielded cables and hermetically sealed cables separately. (4) Terminals with insulation sleeves cannot be arranged as a terminal block, so you should cover the terminals with insulation tubes.
(5) Connect 24 to 22 AWG (1 mm) wires to the input/output terminals. The plastic jackets that are removed from the cables should be 8 mm to 10 mm long. The specifications for the terminals and the wiring of the terminals are shown below. Use only copper leads that can resist temperatures above 60° C /75° C. 24-22AWG 8-10mm (6) Note: use cables with the same length (less than 200 m) and use wire resistance of less than 100 ohm. 4-12