Chapter 4 Analog Output Module AS04DA External wiring Voltage output *4 CH1 CHX -10V~+10V VO1 IO1 AG AC m otor drive, recorder, proportioning valve Shielded cable*1 SLD AG Current output CHX 0mA~20mA CH4 *4 AG *3 4_ 24VDC DC/DC +15V -15V AG 24V Con ve rte r *1. Use shielded cables to isolate the analog input signal cable from other power cables. *2. If variability in the input voltage results in interference within the wiring, connect the module to a capacitor having a capacitance between 0.1 – 0.47 μ F and a working voltage of 25 V. *3. Connect the SLD to FE, and connect both the FE and the terminal to the ground terminal. *4. Every channel can operate with the wiring presented above.
4-13 *2 VO4 IO4 AG SLD AC motor drive, recorder, proporti oni ng val ve Shielded cable*1 FE 0V