AS Series Programming Manual 7.3.3 Troubleshooting for the Module AS00SCM as a Communication Module 7.3.3.1 ERROR LED Indicator Are ON The following error codes identify possible errors when the AS00SCM module is installed on the right side of the CPU module and acts as a communication module. 7.3.3.2 ERROR LED Indicators Blinking Every 0.5 Seconds _7 The following error codes identify possible errors when the AS00SCM module is installed on the right side of the CPU module and acts as a communication module. 7-16 Error Description Solution Code 16#1808 The signal received by channel 1 exceeds the range of analog inputs or the SEN voltage is abnormal.
Check the signal received by channel 1 and the cable connections. 16#1809 The signal received by channel 1 exceeds the weight limit. Check the value input to channel 1 and the maximum weight setting. 16#180A The factory calibration in channel 1 is incorrect. Check the weight calibration in channel 1. 16#180B The signal received by channel 2 exceeds the range of analog inputs or the SEN voltage is abnormal. Check the signal received by channel 2 and the cable connections. 16#180C The signal received by channel 2 exceeds the weight limit. Check the value input to channel 2 and the maximum weight setting. 16#180D The factory calibration in channel 2 is incorrect.
Check the weight calibration in channel 1. Error Description Solution Code 16#1605 Hardware failure 1. Check that the module is securely installed. 2. Install a new AS00SCM or contact your distributor. 16#1606 The function card setting is incorrect. 1. Check if the function card is securely installed. 2. Install a new function card or contact your distributor. 3. Check if the setting in HWCONFIG is consistent with the function card setting. 4. Install a new AS00SCM or contact your distributor. Error Description Solution Code 16#1802 Incorrect parameters Check the parameter in HWCONFIG. Download the parameter again. 16#1803 Communication timeout 1.
Check whether the communication cable is properly connected. 2. Check if the station number and the communication format are correctly set. 3. Check if the connection with the function card is working correctly. 16#1804 The UD Link setting is incorrect. 1. Check the settings of the UD Link. 2. Check the warning settings in the PLC.