Chapter 7 Troubleshooting The following error codes can only be viewed with SCMSoft; when the following errors occur, they are not shown on the LED indicators and the system does not send the error messages to the CPU module. 7.3.4 Troubleshooting for the Module AS00SCM as a Remote Module Errors from the remote modules are regarded as warnings for AS Series CPU modules. The LED indicator of the CPU module blinks and the CPU module can still operate. Use flag SM30 to manage error presentation in the remote modules. 7_ 7.3.4.1 ERROR LED Indicators Are ON Error codes:
7-17 Error Description Solution Code 16#0107 The settings in HWCONFIG and manual settings are not consistent with function card 1. Check the settings in HWCONFIG and manual settings for function card 1. 16#0108 The settings in HWCONFIG and manual settings are not consistent for function card 2. Check the settings in HWCONFIG and manual settings for function card 2. 16#0201 Incorrect parameters Check the parameter in HWCONFIG. Download the parameter again. 16#0301 Function card 1 communication timeout 1. Check if the station number and the communication format are correctly set. 2. Check if the connection with the function card is working correctly.
16#0302 Function card 2 communication timeout 1. Check if the station number and the communication format are correctly set. 2. Check if the connection with the function card is working correctly. 16#0400 Invalid UD Link Group ID for function card 1 1. Check the UD Link settings. 2. Check the warning settings in the PLC. 16#0401 Invalid UD Link Group ID for function card 2 1. Check the UD Link settings. 2. Check the warning settings in the PLC. 16#0402 Invalid UD Link Command for function card 1 1. Check the UD Link settings. 2. Check the warning settings in the PLC. 16#0403 Invalid UD Link Command for function card 1 1. Check the UD Link settings. 2. Check the warning settings in the PLC.
Error Description Solution Code 16#1301 Hardware failure 1. Check if the module is securely installed. 2. Change and install a new AS00SCM or contact your distributor. 16#1302 The function card setting is incorrect. 1. Check if the function card is securely installed with the AS-FCOPM card. 2. Change and install a new function card or contact your distributor. 3. Check if the setting in HWCONFIG is consistent with the function card setting. 4. Install a new AS00SCM or contact your distributor.