Delta Electronics — 7.4.1 Error Codes and LED Indicators for CPU Modules

Chapter 7 Troubleshooting 7.4.1 Error Codes and LED Indicators for CPU Modules Note: refer to Section 12.3 for the status descriptions of the Error LED indicators. 7_ 7-19 Module Type LED indicator Descriptions Warning type: Blinking slowly (every one second and off for three seconds): a warning is triggered, but the system can still run. OFF: a warning is triggered, but the system can still run. You can modify the rules of how a warning is triggered, or use the SM/SR to show the warnings. ERROR LED indicator status Error CPU Description code status Blinking Blinking Blinking ON OFF fast normally slowly 000A Scan timeout Stop V 000C The program in the PLC is damaged.

Stop V 0010 The access to the memory in the CPU is denied. Stop V 0011 The PLC ID is incorrect. Continue V 0012 The PLC password is incorrect. Continue V 0026 RTC cannot keep track of the current time (the battery LED is blinking.) Continue 0027 Battery low (the battery LED is ON.) Continue 002A 24VDC power supply is not sufficient and then is recovered from low-voltage for less than 10 ms. Continue V 002D The PLC maximum password attempts exceeded. Continue V 002E The access to the external memory of the CPU is denied. Stop V 002F PLC programs are not consistent with the system logs. Stop V 0050 The memories in the latched special auxiliary relays are abnormal.

Continue V 0051 The latched special data registers are abnormal. Continue V 0052 The memories in the latched auxiliary relays are abnormal. Continue V 0054 The latched counters are abnormal. Continue V 0055 The latched 32-bit counters are abnormal. Continue V 0056 The latched special auxiliary relay is abnormal. Continue V 0059 The latched data registers are abnormal. Continue V 005D The CPU module does not detect a memory card. Continue V 005E The memory card is initialized incorrectly. Continue V 0063 An error occurs when data is written to the memory card. Continue V 0064 A file in the memory card cannot be read.

Continue V 0070 The actual arrangement of the function cards is not consistent with the settings. Stop V 0102 The interrupt number exceeds the range. Stop V 0202 The MC instruction exceeds the range. Stop V